Product Details:
Payment & Shipping Terms:
|
Rated Output Voltage: | ≤0~1000kV | Frequency Adjustment Sensitivity: | 0.1Hz |
---|---|---|---|
Output Frequency: | 30~300Hz | Working Mode: | Continuous Working |
Quality Factor: | 30~90 | Resonate Voltage Waveform: | Sine Wave, Distortion≤1.0% |
Instability: | <0.05% | Power Source: | Single Phase 220V Or Three Phase 380V±10% |
AC Resonant Test System (For Substation Equipment) / Voltage Withstand Test System
Application:
HZBP-BD is applied for voltage withstand test of capacitive equipment, such as transformer, GIS system, SF6 switch, CT/PT, insulator, busbar, cable and bushing ect. This device is researched and manufactured according to withstand test regulations of 220KV and blow substations primary electrical equipment. The AC/DC voltage withstand test equipment both need satisfy high voltage, small current and low voltage, large current test condition, and with wide application range. HZBP using the principle of series resonant, is composed by variable frequency power source control box(console), excitation transformer, reactor and capacitive voltage divider,compensating capacitor.
Product Features:
1. Flexible configuration. Can equip with different types of reactor to satisfy different tested products. To achieve a multi-purpose machine, highly cost effective.
Product parameters:
Rated Output Voltage | ≤0~1000kV |
Output Frequency | 30~300Hz |
Resonate Voltage Waveform | Sine wave, distortion≤1.0% |
Working Mode | Continuous working |
Quality Factor | 30~90 |
Frequency Adjustment Sensitivity | 0.1Hz |
Instability | <0.05% |
Power Source | Single phase 220V or three phase 380V±10% |
Power frequency 50Hz/60Hz±5% |
Technique index
Serial products and application
Mode | Application(10kV~500kV transformer substation AC voltage withstand equipment, frequency 30~300Hz) | ||||
Frequency Power Source | Resonant Reactor | Excitation transformer | Divider | Application | |
HZBP-BD-50/50/25 | 3kW | 25kV/1A two sets(dry type) | 3kVA(dry type) | 50kV | ≤1000kVA 10kV transformer 10kV switch, busbar, PT, CT ect. 10kV(300mm2) cable≤1.0km |
HZBP-BD-108/108/27 | 5kW | 27kV/1A four sets(dry type) | 5kVA(dry type) | 110kV | ≤31500kVA 35kV transformer 35kV switch, busbar, PT, CT ect. 10kV(300mm2) cable 2km 35kV(300mm2) cable 0.5km |
HZBP-BD-200/200/50 | 10kW | 50kV/1A four sets(dry type) | 10kVA(dry type) | 200kV | ≤50000kVA 110kV transformer 110KV GIS, PT, CT ect.(preventive test) 35kV(300mm2) cable ≤1.0km 10kV(300mm2) cable ≤2.0km |
HZBP-BD-270/270/45 | 15kW | 45kV/1A six sets(dry type) | 15kVA(dry type) | 300kV | ≤50000kVA 110kV transformer 110kV GIS, PT, CT ect. 35kV(300mm2) cable ≤1.2km 10kV(300mm2) cable ≤3.0km |
HZBP-BD-800/400/50 | 30kW | 50kV/2A eight sets(dry type) 100kV/2A four sets(oil immersed) | 30kVA(dry type) 30kA(oil immersed) |
400kV | ≤80000kVA 220kV transformer ≤50000kVA 110kV transformer 110kV/220kV GIS, PT, CT ect. 35kV(300mm2) cable ≤2.0km 110kV(300mm2) cable ≤0.7km |
HZBP-BD-1600/800/200 | 60kW | 200kV/2A four sets(oil immersed) | 60kVA(dry type) | 800kV | ≤80000kVA 220kV transformer ≤50000kVA 110kV transformer 500kV GIS, PT, CT ect. 220kV switch, busbar, PT, CT ect. 110kV(400mm2) cable ≤1.5km 220kV(400mm2) cable ≤1.0km |
Note: can be customized |
Quality Guarantee: One year quality guarantee after shipment.
Contact Person: Tracy
Tel: +8618827048347